DESIGN CALCULATIONS

The required agent quantity is based on the volume of protected area at the lowest expected ambient temperature and concentration required. To obtain the minimum agent quantity required, use the following equation:

 

                      W = (V/S) X ( C/100 -C)                     

 

W = weight of Agent required V = volume of protected area

olume S = 0.1269 + 0.000513 T

C = Required HFC-227ea Design Concentration (% by volume) at Design Temperature (t).

T = Design temperature in protected area (°C)